ABB Cylon BACnet MS/TP Kernel Module (mstp.ko) Out-of-Bounds Write in SendFrame()

Critical
Advisory ID
ZSL-2025-5953
Release Date
22 May 2025
Vendor
Affected Version
<=3.08.03
CVE
N/A
Tested On
GNU/Linux Kernel 5.4.27, GNU/Linux Kernel 4.15.13, GNU/Linux 3.15.10 (armv7l), GNU/Linux 3.10.0 (x86_64), GNU/Linux 2.6.32 (x86_64), Intel(R) Atom(TM) Processor E3930 @ 1.30GHz, Intel(R) Xeon(R) Silver 4208 CPU @ 2.10GHz
Summary

ASPECT is an award-winning scalable building energy management and control solution designed to allow users seamless access to their building data through standard building protocols including smart devices.

BACnet Smart Building Controllers. ABB's BACnet portfolio features a series of BACnet IP and BACnet MS/TP field controllers for ASPECT and INTEGRA building management solutions. ABB BACnet controllers are designed for intelligent control of HVAC equipment such as central plant, boilers, chillers, cooling towers, heat pump systems, air handling units (constant volume, variable air volume, and multi-zone), rooftop units, electrical systems such as lighting control, variable frequency drives and metering.

The FLXeon Controller Series uses BACnet/IP standards to deliver unprecedented connectivity and open integration for your building automation systems. It's scalable, and modular, allowing you to control a diverse range of HVAC functions.

Committee: BACnet.org

InFaq: A BACnet router is a device that passes a message from one network to another without changing the form or content of the message. This kind of device is used to interconnect BACnet networks that have different media (Ethernet, MS/TP over twisted pair, etc.). It is a simple device that just routes BACnet messages where they need to go, without decoding or altering them. A BACnet gateway is a more complex device that is used to interconnect a BACnet network with a non-BACnet network (such as Modbus or KNX). A gateway must decode messages on each network and reformat or translate the information to meet the requirements of the other network to route messages where they need to go. Gateways generally require more configuration, commissioning and maintenance effort than a router, as well as being more costly.

License: GPL Author: Muiz M. Haider Description: BACnet MS/TP Serial Line Discipline :: Master-Slave / Token Passing ::

Description

A buffer overflow vulnerability exists in the mstp.ko kernel module, responsible for processing BACnet MS/TP frames over serial (RS485). The SendFrame() function writes directly into a statically sized kernel buffer (alloc_entry(0x1f5)) without validating the length of attacker-controlled data (param_5). If an MS/TP frame contains a crafted payload exceeding 492 bytes, the function performs out-of-bounds writes beyond the allocated 501-byte buffer, corrupting kernel memory. This flaw allows local or physically connected attackers to trigger denial-of-service or achieve remote code execution in kernel space. Tested against version 3.08.03 with a custom BACnet frame over /dev/ttyS0.

mstp.KOrruption: Kernel Frame Overflow in BACnet MS/TP Module - Memory corruption in embedded RS485 stack.

Proof of Concept
Disclosure Timeline
21.04.2024Vulnerability discovered.
22.04.2024Vendor contacted.
22.04.2024Vendor responds.
02.05.2024Working with the vendor.
21.05.2025No response from the vendor.
22.05.2025Public security advisory released.
Credits
Vulnerability discovered by Gjoko Krstic
References
Changelog
22.05.2025Initial release
26.05.2025Added reference [2]
26.06.2026Added reference [3]